Contec Computer Hardware 4FITGY 1 User Manual

Ver.1.00  
F&eIT Series  
Isolated Digital I/O Module  
DIO-4/4(FIT)GY  
This product is an expansion module (device module) that adds  
digital signal I/O interfaces to one of various types of controllers.  
The product is used in combination with the I/O controller  
module <CPU-CAxx(FIT)GY> (*1) or microcontroller unit  
<CPU-SBxx(FIT)GY> (*1) in the F&eIT Series.  
This product can perform a maximum of 4 points of  
Optocoupler isolated input and 4 points of Optocoupler isolated  
output per module. (Input: 12 - 24 VDC specified, output: 12 -  
48 VDC specified)  
*1 This module is available in different product models. "x" in each model number  
represents a blank or one alphanumeric character. This is applicable to the rest of this  
document.  
* Specifications, color and design of the products are subject to  
change without notice.  
Features  
Specification  
This product can perform 4-point digital signal input and 4-point  
digital signal output, treating 4 points as a group.  
Specifications  
Specifications  
DIO-4/4(FIT)GY  
Item  
Input section  
Input format  
Input section is ready to accept both the current sinking output  
and current source output.  
Optocoupler isolated input  
(compatible with current sink output and current source  
output)  
Input resistance  
Input ON current  
Input OFF current  
3kΩ  
3.4mA or more  
0.16mA or less  
The output section is a high sink current, open collector type  
using high-capacitance transistors.  
150 mA/24 VDC or 50 mA/48 VDC max. (per channel)  
Number of input signal points 4 points (4 points/common)  
Response time Within 1msec  
External circuit power supply 12 - 24VDC (±15%)  
(4mA/12V - 8mA/24V per channel)  
Isolated I/O operations using an optocoupler improves noise  
immunity.  
Output section  
Output format  
Optocoupler isolated open collector output (current sink type)  
12 - 48VDC (±15%)  
150mA (12 - 24V) (per channel) (Max.)  
50mA (36 - 48V) (per channel) (Max.)  
4 points (4 points/common)  
Ratings  
Output voltage  
Output current  
A rotary switch allows you to set device IDs, making it easy to  
keep track of device numbers.  
Number of output signal  
points  
Like other F&eIT series products, the module has a 35mm DIN  
rail mounting mechanism as standard. A connection to a  
controller module can be effected on a lateral, stack basis in a  
unique configuration, which permits a simple, smart system  
configuration without the need for a backplane board.  
Response time  
Within 1msec  
External circuit power supply 12 - 48VDC (±15%)  
Common section  
Interrupt level  
Using CPU-SBxx(FIT)GY: IRQ 5, 7, or 9  
Internal current consumption 5VDC(±5%) 150mA(Max.) *1  
Allowable distance of signal Approx. 50m (depending on wiring environment)  
extension  
Physical dimensions (mm)  
Weight of the module itself  
Module connection method  
25.2(W) x 64.7(D) x 94.0(H) (exclusive of protrusions)  
100g  
Stack connection by means of a connection mechanism  
standard with the system.  
Module installation method  
One-touch connection to 35mm DIN rails  
(standard connection mechanism provided in the system)  
AWG 28 - 16 wire type: 0.32 - 1.30mm  
FRONT-MC 1,5/12-STF-3,81 (made by Phoenix Contact  
Corp.)  
Applicable wire  
Applicable plug  
3.81mm-pitch, rated current: 8A (Max.)  
*1 The stack connector accepts currents of up to 3.0A (Max.).  
Installation Environment Requirements  
Packing List  
Item  
Requirement description  
Operating temperature  
Storage temperature  
Operating humidity  
Floating dust particles  
Corrosive gases  
0 - 50°C  
-10 - 60°C  
10 - 90%RH (No condensation)  
Not to be excessive  
None  
Module[DIO-4/4(FIT)GY] …1  
First step guide … 1  
CD-ROM [F&eIT Series Setup Disk] *1…1  
Interface connector plug…1  
Noise immunity Line-noise AC line/2kV, Signal line/1kV  
*1  
(IEC1000-4-4Level 3, EN61000-4-4Level 3)  
Static  
electricity  
Contact discharge/4kV (IEC1000-4-2Level 2,  
EN61000-4-2Level 2)  
*1 The CD-ROM contains various software and User’s Guide.  
resistance Atmospheric discharge/8kV (IEC1000-4-2Level 3,  
EN61000-4-2Level 3)  
Vibration  
Sweep  
10 - 57Hz/semi-amplitude 0.15mm, 57 - 150Hz/2.0G  
resistance  
resistance 80minutes each in X, Y, and Z directions  
(JIS C0040-compliant, IEC68-2-6-compliant)  
Impact resistance  
15G half-sine shock for 11ms in X, Y, and Z directions  
(JIS C0041-compliant, IEC68-2-27-compliant)  
*1 When using a POW-AD22GY  
DIO-4/4(FIT)GY  
1
 
Ver.1.00  
Example of a Connection to Current Sink Output  
Interface Connector  
Module  
External circuit  
Vcc  
How to Connect an Interface Connector  
When connecting the Module to an external device, you can  
use the supplied connector plug.  
3kΩ  
Minus  
External  
power supply  
12V - 24VDC  
common  
To wire the Module, strip the sheath about 9 - 10mm from an  
end of the wire and insert the exposed wire into an opening.  
Tighten the screw to fasten the inserted wire. Applicable  
wires are AWG28 - 16.  
Input  
pin  
Current sink  
output  
Optocoupler  
X
Turn the screw to fasten the wire.  
0
4
1
5
2
3
7
6
6
Example of a Connection to Current Source Output  
9 - 10mm  
Device  
ID  
2
Module  
External circuit  
COM 0  
NC  
0
Vcc  
- Applicable wire:  
1
3.81mm pitch, 12-pin type, 8.0A rated current  
3kΩ  
2
3
MC1, 5/12-GF-3.81 [made by Phoenix Contact Corp.]  
COM1  
Minus  
X NC  
External  
common  
power supply  
4
5
6
7
- Applicable plug:  
Input  
pin  
Front screw type with connector stopper flange  
FRONT-MC 1,5/12-STF-3,81 [made by Phoenix Contact Corp.]  
Applicable cable: AWG28-16  
Optocoupler  
Current  
source output  
DI-8  
CAUTION  
Removing the connector plug by grasping the cable can  
break the wire.  
Output section  
Figure below shows the output circuit for the interface section  
of this product. The signal output section consists of an  
Optocoupler isolated open collector output (current sink type).  
An external power supply is therefore required to drive the  
output section of this module.  
The maximum output current rating per channel is 150 mA for  
this product (at 12 - 24 VDC) or 50mA for this product (at 36 -  
48 VDC). A surge voltage protection circuit (zener diode) is  
provided for the output transistors of this module. When the  
module drives relays, lamps, and other induction loads,  
however, another surge voltage countermeasure should be  
provided on the load side.  
Signal Layout on the Interface Connector  
The Module can be connected to an external device using a  
12-pin connector that is provided on the Module face.  
Input port  
plus / minus common  
COM 0 --- +/-COM  
N.C.  
X 0 --- IN 0  
X 1 --- IN 1  
Digital Input: 4points  
X 2 --- IN 2  
X 3 --- IN 3  
COM 1 --- +COM  
COM 2 --- -COM  
Y 0 --- OUT 0  
Output port plus common  
Output port minus common  
CAUTION  
Y 1 --- OUT 1  
Digital Output: 4points  
When the power is turned on, all output will be OFF.  
Y 2 --- OUT 2  
Y 3 --- OUT 3  
Output Circuit  
Module  
External circuit  
External I/O Circuits  
Vcc  
Plus  
common  
Load  
Input section  
Output  
pin  
Figure below shows the input equivalent circuit for the interface  
section of this product.  
External  
power supply  
12V - 48VDC  
The signal input section consists of an Optocoupler isolated  
input (compatible with both current sink output and current  
Vcc  
source output).  
An external power supply is therefore  
required to drive the input section of this module. The power  
requirement for the <DIO-4/4(FIT)GY> or <DI-8(FIT)GY> is  
about 8 mA per input channel at 24 VDC (about 4 mA at 12  
VDC).  
Load  
Output  
pin  
Optocoupler  
Minus  
common  
Input Circuit  
Module  
External circuit  
Vcc  
3kΩ  
Connection example:  
Using Inputs X0  
+/-  
common  
External  
power supply  
12V - 24VDC  
Input  
pin  
Input contact  
Optocoupler  
Input plus common (e.g., connector COM0)  
point  
+
External  
power supply  
12V - 24VDC  
-
Input pin (e.g., connector X0)  
3kΩ  
Input  
pin  
Input contact  
point  
Optocoupler  
DIO-4/4(FIT)GY  
3
 
Ver.1.00  
Using Outputs Y0  
+
External  
power supply  
12V - 48VDC  
Load  
Output plus common  
-
Output pin (e.g., connector Y1)  
Output minus common  
Example of Connecting Outputs and Inputs  
External  
power supply  
12V - 24VDC  
-
+
Intput module  
Common plus for intput  
Output module  
Common plus for output  
Output  
Intput  
Common minus for output  
Setting a Device ID  
The controller module distinguishes and keeps track of the  
modules that are connected to it by assigning device IDs to  
them. Each module, therefore, should be assigned a unique  
ID.  
A Device ID can be assigned in a 0 - 7 range, so that a  
maximum of eight modules can be distinguished.  
The factory setting for the Device ID is [0].  
Setup Method  
A Device ID can be set by turning the rotary switch that is  
located on the module face.  
A Device ID can be assigned by turning the switch.  
6
Device  
ID  
Factory setting:  
(Device ID = 0)  
2
DIO-4/4(FIT)GY  
4
 

Conair Hair Dryer 151Z User Manual
Cub Cadet Log Splitter l5 27 cc User Manual
Dymo Printer LT100 H User Manual
Earthquake Sound Stereo Amplifier XJ 600R User Manual
Elation Professional Network Router RMD 1220 User Manual
EverFocus Cable Box EHA SRX User Manual
Everpure Water System EV9100 06 User Manual
Fisher Price Model Vehicle V7867 User Manual
GE Cordless Telephone 16197920 User Manual
GE Monogram Refrigerator ZIFI240PII User Manual